The Context Plus XP95 Zone Monitor with Isolator powers and controls the operation of a zone of up to 20 series 65 conventional fire detectors from a loop of Context Plus analogue addressable detectors and interfaces.

 
 

Standard Features

The Zone Monitor with Isolator is factory preset to return an analogue value of 16 when all detectors on the zone are in quiescent state and 64 when a detector changes to the alarm state. The Zone Monitor with Isolator latches in the alarm state.

A 5.1kΩ end-of-line resistor is fitted to detector cables for open-and short-circuit faults. Alternatively, an active end-of-line monitor may be used in conjunction with diode bases and a capacitor of up to 50μF fitted at the Zone Monitor with isolator wiring terminals.